Site icon Complete Water Solutions

RO System Failure – Low Flow, High Pressure & High Conductivity

commercial ro system, hard water issues, commercial reverse osmosis system

Commercial RO System Failure Due to Hard Water Issues

commercial ro system, hard water issues, commercial reverse osmosis system

Commercial RO System Failure Hard Water Issues

Complete Water Solutions was called out for an emergency to get our client’s  Reverse Osmosis System back up and running. The problem that they were experiencing was High Conductivity, High Pressures & Low Flow.

Emergency RO Service

Upon arrival, it was determined that the RO System had experienced hard water. Complete Water Solutions tested the water to confirm the hard water. Upon further inspection, Complete Water was able to determine that the bypass valve on the softeners had been opened. Once closed the hard water went away. In the meantime, Complete Water Solutions supplied and installed new AK4040F Membranes into the RO System. This lowered the conductivity, pressures and increased flow.

Need Membranes Or Service Contact Complete Water Solutions at info@complete-water.com or (855) 787-4200