Veolia RO Membranes | AK Series | AK8040C

We ship to
Please login or register to see downloads

Description

The A-Series, family of proprietary thin-film reverse osmosis membrane elements are characterized by high flux and high sodium chloride rejection. AK Low Pressure Brackish Water Elements are selected when high rejection and low operating pressures are desired. These elements allow significant energy savings since good rejection is achieved at operating pressures as low as 100 psi (689 kPa).

Typical Operating Pressure: 100 psi (689 kPa)
Typical Operating Flux: 10-20 GFD (15-35 LMH)
Maximum Operating Pressure: 600 psi (4,136 kPa)
Maximum Temperature:

Continuous operation: 122°F (50°C),
Clean In Place (CIP): 122°F (50°C)

pH Range:

Optimum rejection: 7.0-7.5,
Continuous operation: 2.0-11.0,
Clean In Place (CIP): 1.0-13.0(1)

Maximum Pressure Drop:

Over an element: 12 psi (83 kPa)
Per housing: 50 psi (345 kPa)

Chlorine Tolerance: 1,000+ ppm x hours, dechlorination recommended
Feedwater: NTU < 1 SDI 15 < 5

Specifications

Looking for downloads for this product? Follow the two simple steps below.

Step 1
LoginorCreate Account
Step 2

View downloads!

Downloads

Specifications

Manufacturer Veolia
Series AK Series
Model Number AK8040C
Part Number 1206819
Description Average Permeate Flow GPD (m3): 10,000 (37.9)
Average NaCL Rejection: 99.0%
Minimum NaCL Rejection: 98.0%
Membrane Area Ft2 (m2): 380 (35.3)
Outer Wrap: Cage
Type: Female
Shipping Weight 35 Lbs (16 KG)
Overall Length 40.0 IN (101.6 CM)
Overall Height 7.9 IN (20.1 CM)
Notes CENTRAL TUBE: 1.125 IN (2.86 CM)

Click To Schedule a Service Call

Click To Schedule a Sales Call

Call for a FREE Quote Today

(855) 787-4200